SmartLine STG800 Gauge Pressure Transmitter
Product Info
SmartLine STG800 – Gauge Pressure
Part of the SmartLine® family of products, the STG800 and STG80L are high performance gauge pressure transmitter featuring piezoresistive sensor technology combining pressure sensing with on chip temperature compensation capabilities providing high accuracy, stability and performance over a wide range of application pressures and temperatures. The SmartLine family is also fully tested and compliant with Experion® PKS providing the highest level of compatibility assurance and integration capabilities. SmartLine easily meets the most demanding application needs for pressure measurement applications.
Key Features
- Accuracies up to 0.0375 of span standard & 0.025 of span optional.
- Stability up to 0.015% of URL per year for 15 years
- Automatic temperature compensation
- Rangeability up to 100:1
- Response times as fast as 80ms
- Multiple local display capabilities
- External zero, span, & configuration capability
- Polarity insensitive electrical connections
- Comprehensive on-board diagnostic capabilities
- Integral Dual Seal design for highest safety based on ANSI/NFPA 70-202 and ANSI/ISA 12.27.1
- Full compliance to SIL 2/3 requirements.
- Modular design characteristics
- Available with additional 15-year warranty
- Plugged Impulse Line Detection Option
- Dual/Triple Calibration Option (HART & Fieldbus Only)
Communications/Output Options
- 4-20 mA
- Honeywell Digitally Enhanced (DE)
- HART ® (version 7.0)
- FOUNDATION™ Fieldbus
Honeywell STG840-E1GS4A-1-A-EHE-13S-B-21A0-F1,FE-0000 | Pressure Transmitter | SmartLine STG840 | Gauge; Dual Head | 500 psi Pressure Range (URL) | 0.0375 Accuracy
Item Specifications
-
0.0375
-
0.025
-
ANSI/NFPA 70-202 and ANSI/ISA 12.27.1
-
1/2 Inch
-
NPT Female
-
FOUNDATION Fieldbus: Steady state current - 17.6 mA, Software download current - 27.4 mA
-
316L Stainless Steel
-
Multiple LCD
-
316 Stainless Steel
-
HART: 0 to 1440 ohms, DE: 0 to 1200 ohms
-
185 °F
-
257 °F
-
100:1
-
-40 °F
-
-40 °F
-
500 psi
-
-1
-
-14.7
-
35
-
500
-
80 ms
-
SmartLine STG840
-
0.35
-
5
-
0.01
-
HART: 10.8 to 42.4 VDC, DE: 15 to 49.3 VDC, FOUNDATION Fieldbus: 9 to 32 VDC
-
-40 to 257 °F
-
Gauge, Dual Head