SmartLine STD800 Differential Pressure Transmitter
Product Info
SmartLine STD800 – Differential Pressure
Part of the SmartLine® family of products, the STD800 is a high performance differential pressure transmitter featuring piezoresistive sensor technology. By combining differential pressure sensing with on chip static pressure and temperature compensation the STD800 offers high accuracy and stability over a wide range of application pressures and temperatures. The SmartLine family is also fully tested and compliant with Experion ® PKS providing the highest level of compatibility assurance and integration capabilities. SmartLine easily meets the most demanding application needs for pressure measurement applications.
Key Features
- Accuracies up to 0.035% of span standard & 0.025% of span optional
- Stability up to 0.01% of URL per year for 15 years
- Automatic static pressure & temperature compensation
- Rangeability up to 400:1
- Response times as fast as 90ms
- Multiple local display capabilities
- External zero, span, & configuration capability
- Polarity insensitive electrical connections
- Comprehensive on-board diagnostic capabilities
- Integral Dual Seal design for highest safety based on ANSI/NFPA 70-202 and ANSI/ISA 12.27.0
- World class overpressure protection
- Full compliance to SIL 2/3 requirements.
- Modular design characteristics
- Available with additional 15-year warranty
- Plugged Impulse Line Detection Option
- Dual/Triple Calibration Option (HART & Fieldbus only)
Communications/Output Options
- 4-20 mA
- Honeywell Digitally Enhanced (DE)
- HART ® (version 7.0)
- FOUNDATION™ Fieldbus
Honeywell STD830-51AS4AS-1-A-CD0-11S-A-00A0-00-0000 | Pressure Transmitter | SmartLine STD830 | Differential | 100 psi Pressure Range (URL) | 0.0375 Accuracy
Item Specifications
-
0.0375
-
0.0325
-
ANSI/NFPA 70-202 and ANSI/ISA 12.27.0
-
1/4 Inch
-
NPTF Female
-
FOUNDATION Fieldbus: Steady state current - 17.6 mA, Software download current - 27.4 mA
-
Gold Plated Hastelloy C-276
-
Multiple LCD
-
316 Stainless Steel
-
HART: 0 to 1440 ohms, DE: 0 to 1200 ohms
-
185 °F
-
257 °F
-
100:1
-
-40 °F
-
-40 °F
-
100 psi
-
-7
-
-100
-
7
-
100
-
90 ms
-
SmartLine STD830
-
0.07
-
1
-
0.02
-
HART: 10.8 to 42.4 VDC, DE: 15 to 49.3 VDC, FOUNDATION Fieldbus: 9 to 32 VDC
-
-40 to 257 °F
-
Differential